Low-Voltage DC Power Distribution for Data Center Infrastructure
About This Document
This Open Compute Project white paper examines low-voltage DC (LVDC) power-distribution architectures for data centers amid rapid growth in AI workloads and rack power density. It compares staged pathways from conventional AC power to DC distribution, covering power-conversion boundaries, grounding, protection, energy storage, reliability, and grid interaction. Rather than prescribing a single topology, the document establishes a technical framework for data center operators, designers, manufacturers, utilities, and regulators.
Key Takeaways
- Growing AI workloads, highly dynamic demand, and increasing rack densities are making efficiency, scalability, and grid interaction critical constraints for traditional AC architectures.
- LVDC can reduce the number of power-conversion stages, make more effective use of conductors, and simplify energy-storage integration, although the ultimate benefit depends on the specific topology, load profile, and maturity of the equipment ecosystem.
- DC-powered HPR v4 raises single-shelf capacity to 100 kW; further scaling is constrained by the existing 50 VDC vertical busbar, prompting consideration of raising in-rack distribution voltage to 800 VDC.
- The familiar UPS maintenance bypass cannot simply be carried over to LVDC: redundancy must be provided at the power-block and/or distribution level, potentially with a DC static transfer switch further upstream.
- The choice among AC, hybrid, and DC architectures should account for availability requirements, grounding, fault protection, voltage standards, local practices, and the availability of compatible equipment.
Key Figures
- Initial release date
- 30 марта 2026
- Document length
- 155 страниц
- Upper limit of LVDC
- ≤1 500 VDC
- HPR v1 capacity
- 33 kW
- HPR v2 capacity
- 72 kW
- HPR v4 capacity
- 100 kW
- HPR v4 power-density increase
- 39 %
- IT rack space released
- примерно 12–16 OU
- Increase in available IT rack space
- 27–36 %
- Existing vertical busbar voltage
- 50 VDC
- Example in-rack DC distribution voltage
- 800 VDC
- Example AI load served by one MV-to-LV power block
- 3+ MW
- Target availability for AI training data centers
- 99,9 %
- Target availability for AI inference data centers
- 99,999 %
- Assumed data center service life
- около 10 лет
- NExT Factory operating range
- до 750 VDC
- EU Low Voltage Directive DC range
- 75–1 500 VDC
- Energy-use reduction in the BMW example
- 8,8 %
- Minimum voltage for potential corona discharge
- 300 V
- Sustained overvoltage requirement for DER
- 110 %
Version 1.0 and the document’s first release.
Document pagination.
The document’s defined scope for low-voltage DC distribution.
AC-powered power shelf in an ORv3 HPR rack.
AC-powered power shelf in an ORv3 HPR rack.
DC-powered power shelf using the Mt. Diablo Power Rack.
Stated increase in power per power shelf, partly enabled by eliminating AC/DC conversion.
Space made available by moving in-rack energy storage to the Power Rack.
Additional compute capacity in a rack of the stated height after relocating energy storage.
Identified as a constraint on further in-rack power scaling.
Stage 1a reduces this voltage to a level below the existing vertical-busbar voltage.
Illustrative scale of the supplied AI load.
Stated target availability level for training environments.
Stated target availability level for inference environments.
Used to assess failure rates and the need for spare equipment.
Symmetrical two-wire DC distribution.
Applicability range of the EU Low Voltage Directive.
DC-powered manufacturing cell after nearly two years of operation compared with AC.
May occur at sharp edges, defects, and low pressure.
Requirement for distributed energy resources; also applied to grid-forming operation in islanded mode under UL 3001.
Practical Value for Data Center Owners
For data center owners and project teams, this paper provides a baseline technical benchmark for evaluating LVDC at AI facilities: comparing conversion stages, BBU placement, busbar voltage, and redundancy requirements against a conventional AC design. It is particularly useful during conceptual design and engineering phases for determining whether a 50 VDC busbar becomes a constraint in high-density racks, and for choosing between 800 VDC in-rack distribution and broad-range distribution up to 1,500 VDC. The central design risks are protection, grounding, AC/DC conversion resilience, and the absence of a conventional UPS maintenance bypass in LVDC topologies.
Where It Applies
Topics
Source: Open Compute Project Foundation · open page